STEP1 to SF2 of the (R410A) is use the 0.6L, reason to be 1L strong need in the STEP2 (R32) is the following. ① the influence of the density difference (slightly) ② impact line-up has increased of the indoor unit (slightly) impact due to the characteristics of ③R32 (majority) ... conventional, initial filling amount of refrigerant in the performance securing a standard pipe length 7.5m but I think that it is determined, R32 on the refrigerant properties, in order to discharge pipe temperature is likely to rise, and the accumulator is empty when you have exceeded the local piping length 7.5m, work is immediately discharge pipe droop, extremely ability There is a possibility that the fall. By the discharge pipe temperature droop in the long piping, after assessing how much capacity is fall, determined amount of 7.5m the initial refrigerant amount + α but we believe it is necessary to make the [Kg], alpha [Kg] is you will need about 0.5kg is a difference of 7.5m ~ 30m at the maximum.